How To Test An Electrical PLC Panel

 

How-To-Test-An-Electrical-PLC-Panel, Testing-Of-PLC-Panel


18 May, 2021.

In this post, we will see the basics of testing an electrical PLC panel.

Every new programmer in industrial automation must understand the basic principle of testing an electrical PLC panel. Without it, he cannot be able to further troubleshoot or understand complex automation systems. PLC is always installed in an electrical panel; it does not come as standalone unit. Because, as the PLC is a combination of hardware and software; if you only know to troubleshoot a software program but do not have any idea of the IO’s of PLC or the wiring which is done with PLC, then  it will be a half knowledge for you. So, it is necessary to understand how to check an electrical PLC panel.

The panel consists of many components apart from a PLC; like circuit breakers, contactors, relays, terminal boards, bus bar, transformers, line chokes, VFD, fuses and power supplies. All these can be termed as supporting components, for PLC as well as field wiring. If the wiring is not proper, then you will neither be able to power up the PLC properly; nor the field devices and equipment. So, let us have a look at step by step basics of testing the panel.

How to power up the PLC panel for first time:

Hey, do not proceed instantly to power up the panel. Quick hurry can damage the panel, because there can be chances of short circuit wiring or wrong wiring. So, before turning on the mains supply, it is preferred that you check the continuity of wires and connections. Keep all the switches, breakers, and fuses in open position (means off position). This will ensure that all the circuits are open and not connected with each other. Keep the mains power breaker off as of now. Connect a multimeter and check the incoming voltage in the main power breaker. The voltage between each phase to phase and each phase to neutral must be proper. Once you have confirmed the voltage, check the continuity of the wires according to the panel drawing. Basically, this ensures that the wiring that you have done is proper and will not cause any issue when the panel is powered up.

Next, check the voltage between earths to neutral. It must be typically less than 0.5 V. This ensures that there will not be any electrical noise in the panel when it is powered up. Because, if noise exists in the panel, then it will cause abrupt disturbances in the signals received or sent with respect to PLC. And if the noise is extreme, then it can damage either the instrument or the PLC IO. Then, check the power earthing and instrument earthing. Both the earthing should be separate and there should not be any continuity between them.

Now, you can power up the PLC. Turn on the mains power breaker and turn on all the breakers and switches one by one. This means that now, the PLC panel has been charged up properly. Check the voltage at each and every breaker, switch and fuse when powered up. This shows that proper voltage is present at every point.

How to check the inputs and outputs of PLC:

Now, you have to check the IO’s of the PLC. According to the wiring that you have done, check digital inputs first. On giving the input at the desired terminal point in the panel or somewhere else, the corresponding PLC input address in the program must be turned on. Then, check the digital outputs. According to the PLC output address that you have turned on, the physical PLC output must also turn on. When it is on, check the output voltage across it. The output is connected to a relay board mostly. If the relay turns on, then check whether it’s output is given to a contactor or terminal board. The final objective is to check the output voltage coming across the terminals. Then, check the analog inputs. On giving the input, the corresponding PLC input address in the program must be show analog counts accordingly. Then, check the analog outputs. According to the PLC output address that you have given counts, the physical PLC output must also give the corresponding counts. Check the current or voltage across the terminals where the wire is connected.

Once the IO’s have been tested, you now to check the communication protocols used in the panel. For example, if you have used a PLC along with HMI on Modbus TCPIP, check the communication between them. Accordingly, if there are other protocols of communication used for field devices in the panel, then check them too properly.

After this, you can verify that the panel has been tested properly. 

Reference articles for more understanding written by me:

·         Factory Acceptance Test of a PLC panel:


·         Site Acceptance Test:


·         How to check the digital inputs and outputs of a PLC:



·         How to check the analog inputs and outputs of a PLC:


I have covered the general example of panel testing. I have also not attempted to cover every theory of these testing deeply; you can learn it easily once you get familiar with them. I have just given you an insight of these types of controls. Once you are done with these, I am hopeful you will be easily able to understand any testing properly. Learn the basics and explore a new type of study in this type of automation. It will take some practice and as you go on testing the panels, you will become more familiar with it.

Thank you guys; I hope you enjoyed reading the practices normally used for this type of study in industrial automation.

Comments